Code of Federal Regulations · Section
§ 127.205 — Emergency Shutdown
33 C.F.R. § 127.205
View:
Each transfer system must have an emergency shutdown system that—
(a) Can be activated manually; and
(b) Is activated automatically when the fixed sensors under § 127.201(b) measure LNG concentrations exceeding 40% of the lower flammable limit.
Authorizing Statute
-
Procedure33 U.S.C. § 1504
-
Waterfront safety46 U.S.C. § 70011