Code of Federal Regulations · Section

§ 127.205 — Emergency Shutdown

33 C.F.R. § 127.205

View:

Each transfer system must have an emergency shutdown system that—

(a) Can be activated manually; and

(b) Is activated automatically when the fixed sensors under § 127.201(b) measure LNG concentrations exceeding 40% of the lower flammable limit.

Authorizing Statute