Code of Federal Regulations · Section

§ 761.310 — Collecting The Sample

40 C.F.R. § 761.310

View:

Use the standard wipe test as defined in § 761.123 to sample one 10 centimeter by 10 centimeter square (100 cm

2) area to represent surface area PCB concentrations of each square meter or fraction of a square meter of a nearly flat, non-porous surface. For small surfaces, use the same procedure as for the standard wipe test, only sample the entire area, rather than 10 centimeter by 10 centimeter squares.