§ 34.50-10 — -10 Location, Number, And Installation Of Fire Extinguishers—Tb/all

46 C.F.R. § 34.50-10

View:

(a) Approved portable and semi-portable extinguishers must be installed in accordance with table 1 to § 34.50-10(a). The location of the equipment must be, in the opinion of the Officer in Charge, Marine Inspection, convenient in case of emergency. Where special circumstances exist, not covered by table 1 to § 34.50-10(a), the Officer in Charge, Marine Inspection, may require additional equipment as deemed necessary for the proper protection of the vessel.

(b) For additional portable extinguishers as a substitute for sand, see § 34.55-10.

(c) Semi-portable extinguishers must be located in the open so as to be readily seen.

(d) If portable extinguishers are not located in the open or behind glass so that they may be readily seen they may be placed in enclosures together with the firehose, provided such enclosures are marked as required by § 35.40-25 of this subchapter.

(e) Portable extinguishers and their stations must be numbered in accordance with § 35.40-25 of this subchapter.

(f) Portable or semi-portable extinguishers which are required by their nameplates to be protected from freezing must not be located where freezing temperatures may be expected.

(g) Semi-portable extinguishers must be fitted with a suitable hose and nozzle, or other practicable means, so that all portions of the space concerned can be protected.

(h) Table 1 to § 34.50-10(a) indicates the minimum required number and type for each space listed. Extinguishers with larger numerical ratings or multiple letter designations may be used if the extinguishers meet the requirements of the table.

Table 1 to § 34.50-10(a)—Portable and Semi-Portable Extinguishers

Authorizing Statute