§ 76.33-10 — -10 Location And Spacing Of Accumulators
46 C.F.R. § 76.33-10
View:
(a) Smoke accumulators must be located overhead in each compartment. Where liable to physical damage, the accumulators and piping must be suitably protected.
(b) No spot on the overhead of a protected space may be more than 40 feet from an accumulator.
(c) Accumulators must not be located closer to the opening of a ventilator than three times the diameter or equivalent diameter of the opening.