Code of Federal Regulations · Section
§ 112.55-15 — -15 Capacity Of Storage Batteries
46 C.F.R. § 112.55-15
View:
(a) A storage battery for an emergency lighting and power system must have the capacity—
(1) To close all watertight doors two times;
(2) To open all watertight doors once; and
(3) To carry the remaining emergency loads continuously for the time prescribed in § 112.05-5(a), table 112.05-5(a).
(b) At the end of the time specified in paragraph (a) of this section, the potential of the storage battery must be at least 88 percent of the standard voltage.
Authorizing Statute
-
Regulations46 U.S.C. § 3306