Code of Federal Regulations · Section
§ 153.284 — Characteristics Of Required Quick Closing Valves
46 C.F.R. § 153.284
View:
A remotely actuated quick closing shutoff valve required by § 153.530(n) must:
(a) Be a positive shutoff valve;
(b) Be of the fail-closed type that closes on loss of power;
(c) Be capable of local manual closing;
(d) Close from the time of actuation in 30 seconds or less; and
(e) Be equipped with a fusible element that melts at less than 104 °C (approx. 220 °F) and closes the valve.
Authorizing Statute
-
Administration and enforcement33 U.S.C. § 1903
-
General regulatory authority49 U.S.C. § 5103
-
Regulations46 U.S.C. § 3703